Jump to content

St Helens power station

Coordinates: 53°27′02″N 02°44′54″W / 53.45056°N 2.74833°W / 53.45056; -2.74833
From Wikipedia, the free encyclopedia
St Helens power station
Map
CountryEngland
LocationSt Helens, Merseyside
Coordinates53°27′02″N 02°44′54″W / 53.45056°N 2.74833°W / 53.45056; -2.74833
StatusDecommissioned
Construction began1894
Commission date1896
Decommission date1960s
OwnersSt Helens Corporation
(1894–1948)
British Electricity Authority
(1948–1955)
Central Electricity Authority
(1955–1957)
Central Electricity Generating Board
(1958–1970)
OperatorAs owner
Thermal power station
Primary fuelCoal
Secondary fuelFuel Oil
Turbine technologySteam turbines
Cooling towers6
Cooling sourceCirculating water
Power generation
Units operational1 x 5 MW, 1 x 6.5 MW, 1 x 12.5 MW
Make and modelOerlikon, Brush Ljungstrom, Metropolitan Vickers
Nameplate capacity24 MW
Annual net output35,491 MWh (1946)

St Helens power station supplied electricity to the Borough of St Helens and the surrounding area from 1896 to the late 1960s. The power station was developed by the St Helens Corporation which operated it up to the nationalisation of the British electricity supply industry in 1948. It was redeveloped several times to meet the increased demand for electricity.

History

[edit]

St Helens Corporation applied in 1894 for a Provisional Order under the Electric Lighting Acts to generate and supply electricity to Borough of St Helens. An Order was granted by the Board of Trade and was confirmed by Parliament through the Electric Lighting Orders Confirmation (No. 1) Act 1894 (57 & 58 Vict. c. xlix).[1] A power station was built in Warrington Road, St Helens and was commissioned in October 1896. The Corporation charged 6d./kWh and attracted just 63 customers in its first year of operation.[2][3]

In 1897 the Corporation assumed control of St Helens Tramways which it intended to redevelop using electric traction instead of steam power. The Corporation applied for a further Provisional Order in 1900. This was granted and confirmed by Parliament through the Electric Lighting Orders Confirmation (No. 5) Act 1900 (63 & 64 Vict. c. xlix).[4] A new power station built at Croppers Hill, St Helens (53°27’02”N, 2°44’54”W).[5]

The generating station was extended with new plant as demand for electricity grew. In 1911 a 1,500 kW turbo-alternator and condenser were installed costing £5,000.[6] In 1912 a 2,000 kW 6 kW turbo-alternator and associated boilers were installed.[7]

During the general strike in 1926 the local Civil Commissions overruled the St Helen Labour Council and allowed staff to continue to run the power station against the Council’s wishes.[8]

The tram system was decommissioned on 31 March 1936.[9]

The British electricity supply industry was nationalised in 1948 under the provisions of the Electricity Act 1947 (10 & 11 Geo. 6 c. 54).[10] The St Helens electricity undertaking was abolished, ownership of St Helens power station was vested in the British Electricity Authority, and subsequently the Central Electricity Authority and the Central Electricity Generating Board (CEGB).[11] At the same time the electricity distribution and sales responsibilities of the St Helens electricity undertaking were transferred to the Merseyside and North Wales Electricity Board (MANWEB)

Following nationalisation St Helens power station became part of the St Helens electricity supply district.[12]

The power station was converted to oil firing in 1963.[13]

St Helens power station was closed in the late 1960s.[14]

Equipment specification

[edit]

The plant in the original power station was rated at 145 kW and comprised Robey horizontal engines coupled directly to alternators.[3][2]

Plant in 1923

[edit]

By 1923 the plant comprised boilers delivering 161,000 lb/h (20.3 kg/s) of steam to:[15]

  • 1 × 1,000 kW steam turbo-alternator alternating current (AC)
  • 1 × 2,000 kW Dick, Kerr and Company steam turbo-alternator AC[7]
  • 1 × 3,000 kW steam turbo-alternator AC
  • 1 × 5,000 kW steam turbo-alternator AC
  • 1 × 200 kW reciprocating engine with direct current (DC) generator
  • 2 × 300 kW reciprocating engines with DC generators

These machines had a total generating capacity of 11,800 kW comprising 11,000 kW of alternating current (AC) plus 800 kW of direct current (DC) plant.[15]

The following electricity supplies were available to consumers:

  • 400 & 230 Volts, 3-phase, 50 Hz AC
  • 460 & 230 Volts, DC
  • 500 Volts DC, traction current

Plant in 1954

[edit]

By 1954 the plant comprised:[12]

  • Boilers:
    • 5 × Babcock & Wilcox 38,000 lb/h (4.79 kg/s) chain grate stoker boilers (total evaporative capacity 190,000 lb/h (23.9 kg/s)), steam conditions were 265 psi and 750°F (18.3 bar and 399°C), steam was supplied to:
  • Generators:
    • 1 × 5.0 MW Oerlikon turbo-alternator
    • 1 × 6.5 MW Brush Ljungstrom turbo-alternator
    • 1 × 12.5 MW Metropolitan Vickers turbo-alternator

The total generating capacity was 24 MW at 6.6 kV.[12]

Condenser water was cooled in six wooden cooling towers with a total capacity of 1.11 million gallons per hour (1.40 m3/s).[12]

Operations

[edit]

Operating data 1921–23

[edit]

The electricity supply data for the period 1921–23 was:[15]

St Helens power station supply data 1921–23
Electricity Use Units Year
1921 1922 1923
Lighting and domestic MWh 503 584 717
Public lighting MWh 44 43 40
Traction MWh 1,413 1,395 1,559
Power MWh 19,537 11,166 16,820
Bulk supply MWh 0 0 0
Total use MWh 21,497 13,188 19,136

Electricity Loads on the system were:

Year 1921 1922 1923
Maximum load kW 5,713 4,382 5,400
Total connections kW 8,936 10,192 11,298
Load factor Per cent 51.2 43.1 48.9

Revenue from the sale of current (in 1923) was £76,375; the surplus of revenue over expenses was £30,894.[15]

Operating data 1946

[edit]

In 1946 St Helens power station supplied 35,491 MWh of electricity; the maximum output load was 19,486 kW. The load factor was 20.8 %, and the thermal efficiency was 14.13 %.[16]

Operating data 1954–67

[edit]

Operating data for the period 1954–67 was:[12][17]

St Helens power station operating data, 1954–67
Year Running hours or load factor (per cent) Max output capacity  MW Electricity supplied MWh Thermal efficiency per cent
1954 4095 16 34,169 12.98
1955 3129 16 21,744 11.73
1956 3842 16 24,724 12.85
1957 4263 16 28,073 13.48
1958 1288 16 9,829 12.85
1961 1.8 % 16 2,527 10.51
1962 2.0 % 16 2,811 8.92
1963 4.34 % 16 6,080 13.17
1967 4.2 % 16 5,922 10.43

St Helens Electricity District

[edit]

Following nationalisation in 1948 St Helens power station became part of the St Helens electricity supply district, covering 36 square miles (93.2 km2) with a population of 131,000 in 1958. The number of consumers and electricity sold in the St Helens district was:[12]

Year 1957 1958
Number of consumers 36,422 37,079
Electricity sold MWh 380,362 414,369

In 1958 the number of units sold to categories of consumers was:[12]

Type of consumer No. of consumers Electricity sold MWh
Domestic 34,234 53,351
Shops and Offices 2,378 15,677
Factories 187 339,77
Farms 274 1,525
Traction 1 1,893
Public lighting 5 2,151
Total 37,079 414,369

The maximum demand on the system was 93,000 kW, the load factor was 50.9 %.

See also

[edit]

References

[edit]
  1. ^ "Local Acts 1894". Legislation.gov.uk. Retrieved 18 December 2020.
  2. ^ a b "St Helens Star". 23 October 2014. Retrieved 18 December 2020.
  3. ^ a b Garcke, Emile (1898). Manual of Electrical Undertakings 1898-99 vol. 3. London: P. S. King and Son. p. 294.
  4. ^ "Local Acts 1900". Legislation.gov.uk. Retrieved 18 December 2020.
  5. ^ Ordnance Survey 25 inch England and Wales, Lancashire CVII.4 (Eccleston; St Helens), revised 1906, published, 1908
  6. ^ "Lancashire". The Times. 9 April 1911. p. 22.
  7. ^ a b "Industry and Invention". The Times. 21 August 1912. p. 16.
  8. ^ Hannah, Leslie (1979). Electricity before Nationalisation. London: Macmillan. p. 272. ISBN 0333220862.
  9. ^ Klapper, Charles F. (1962). The Golden Age of Tramways. Routledge and Kegan Paul.
  10. ^ "Electricity Act 1947". Legislation.gov.uk. Retrieved 18 December 2020.
  11. ^ Electricity Council (1987). Electricity supply in the United Kingdom: a Chronology. London: Electricity Council. pp. 60–61. ISBN 085188105X.
  12. ^ a b c d e f g Garrett, Frederick (1959). Garcke's Manual of Electricity Supply vol. 56. London: Electrical Press. pp. A-91 A-133 B-224.
  13. ^ CEGB Annual Report 1963, CEGB Statistical Yearbook 1967
  14. ^ The power station is mentioned in the CEGB Statistical Yearbook 1967 but not in the 1972 edition
  15. ^ a b c d Electricity Commissioners (1925). Electricity Supply – 1920–23. London: HMSO. pp. 78–81, 308–13.
  16. ^ Electricity Commissioners (1947). Generation of Electricity in Great Britain year ended 31 December 1946. London: HMSO. p. 13.
  17. ^ CEGB Annual Report 1961–63, CEGB Statistical Yearbook 1967